• Jansen steel-glass-doors as smoke protection doors according to DIN 18095.

  • Fire protection doors T30/ EI30 and T90/ EI90 according to DIN 4102.

  • F30 and F90 fixed glazings according to DIN 4102-13.

Jansen Fire Protection has a wide product range of steel-glass tubular frame doors to meet any possible requirements.

Jansen smoke protection doors according to DIN 18095 are with an installation depth of 50 mm or 60 mm a complete door system with fittings and accessories for flush single or double smoke protection doors, with or without lateral sections and top lights.

Jansen fire protection doors according to DIN 4102, thermally divided steel profiles with an installation depth of 60 mm, are a complete profile system with fittings and accessories for flush single and double fire protection doors, fire protection glazing and doors in glass walls. The outer appearance of the Jansen fire protection door is coincident with the flush Jansen smoke protection door.

The design of the Jansen doors stands out through their narrow profiles along with the largest possible amount of glass. The doors fulfil the highest requirements on technical functionality and extreme continuous load. The door profiles with the requirement RS (smoke protection), T30 and T90 (EI30 – EI90) can be combined with the F30 as well as the F90 profiles for glass walls. The installation depths for the door frame and the door leaf are 50 mm, 60 mm or 70 mm, depending on the system.

Starting Material:

  • hot-dip zinced strip steel
  • colour coating in RAL or DB colours according to customers’ requests
Steel-glass-doors
Steel-glass-doors
Steel-glass-doors
Steel-glass-doors
  • RS

  • T30/ T30 RS

  • T90/ T90 RS

  • Fireprotection glazing F30/ F90

Aesthetics/ Dimensions:

  • smallest profile cross section: box width 25/50 mm
  • measure of blind frame / wing only 130 mm
  • installation depth wing and frame 50, 60 or 70 mm, depending on the system, flush

Opening Manners of Doors:

Hinged doors, opening to the in- and outside.

Approved/ verified according to:

  • RS doors: DIN 18095-1
  • T30: DIN 4102-5
  • T30/ RS: DIN 4102-5 and DIN 18095-1
  • F30: DIN 4102-13
  • T90: DIN 4102-5
  • T90/ RS: DIN 4102-5 and DIN 18095-1
  • F90: DIN 4102-13
  • soundproofing: DIN 4109
  • burglary protection (WK):
    DIN EN 1627
    WK1, WK2 and WK3
  • escape door locks:
    DIN EN 179/ DIN EN 1125 for fire and smoke protection doors
  • gunshot penetration obstructing constructions FB4:
    DIN EN 1522/ 1523